Outlets for Washer/Dryer Combo | Information by Electrical ...
Sep 11, 2017 · Hello, If there is a stacked Washer/Dryer combo in a dedicated closet do i need to have one receptacle for washer and one for the dryer or one 30A-2P will take care of both the washer and the dryer? 210.11C(2) says that i need to have at least one additional 20 amp branch circuit to supply the...
30A/2P stacked washer/dryer...is 20A laundry circuit still required?
Mar 11, 2010 · I have been double dipping in my calcs, counting the 1500W laundry circuit plus the full 30A/2P washer/dryer load. I think going forward I should continue showing the laundry circuit with the "eliminate it if you can" note, but should stop calculating the laundry circuit twice - just go with the 30A/2P load only.
location for stack dryer outlet | Information by Electrical ...
Apr 11, 2017 · Hi , Ive never ran the circuit for one of the stack type washer dryer combinations . I am told they use the same 230 v 30 amp plug and cord as a regular dryer and the washer is on the same circuit . My question is what is the best location as far a height and centering on the closet back wall for the dryer outlet .
stackable washer/dryer circuits | Information by Electrical ...
Jan 24, 2023 · My neighbor purchase a new "stackable" LG combo and it has the two power supply cords (120 washer,,,,240 dryer) The old unit was stacked and had just the one 240 4-wire supply. the voltage was split inside the unit to supply the controls and washer. Anywhoo,,, it is a old home, it has a 4-wire 30amp circuit supplying the closet.
Miele stackable Washer & Dryer | Information by Electrical ...
Dec 12, 2010 · Both washer and dryer had nema 14-30R male plugs and there wasn't a rec. on the back of the dryer as in the Bosch that Dennis wired. I did a little digging on the web and I think the washer is a Miele W3033 and the dryer is a Miele T8003.
Maximum dryer cord length and NEC | Information by Electrical ...
Apr 8, 2017 · If you are not rewiring the house, there is no inspection, no Code issue with using a 10' cord. The HO moving the washer/dryer or going to a stacked unit does create a violation if the receptacle is further away than required, but that is not on the EC any more than them building shelves across or piling stuff in front of the panel is.
All-in-One Washer/Dryer with Inverter HeatPump Load …
Sep 12, 2024 · For projects using such combination washer/dryer, do we need to account for it as an electric dryer load (5000VA-220.54), or do we consider it as a Laundry Circuit load (220.52B) for the dwelling unit service calculation.
Apartment panel sizing | Information by Electrical Professionals for ...
Oct 5, 2010 · Wash/Dryer (electric) 5440VA (includes the two motors and the heater element) Stackable unit Total VA 29,522 VA = 29.52VA 100% first 10KVA and 40% of remainder = 17.81 KVA 100% of the HVAC (largest of the section) 2.60 KVA.70 KVA Furnace blower motor Total 21.11 KVA @ 208v single phase = 101.49 amps is this alll correct?
Laundry Dryer requires AFCI GFCI protection? | Information by ...
Aug 13, 2023 · Looked for an answer online and found that topic, so the correct answer seems to be: in dwelling units dryer receptacle should be GFCI protected NEC 2020 210.8(A) Dwelling Units.
Stack unit washer and dryer | Information by Electrical …
Apr 22, 2015 · IMO, there is a required 120V receptacle needed for the washer and since it is closer than 6' to a sink it would require gfci. The 240V 30 amp receptacle does not require one. rcarroll